PANASONIC HP 12 kW 400V KIT WC12H9E8 heat pump
Product Description
PANASONIC HP 12 kW 400V KIT WC12H9E8 heat pump
|
| |
| 12 kW | |
Kit | KIT-WC12H9E8 | |
Heating capacity (A +7°C, W 35°C) | kW | 12,00 |
COP (A +7°C, W 35°C) | 4,74 | |
Heating capacity (A +7°C, W 55°C) | kW | 12,00 |
COP (A +7°C, W 55°C) | 2,88 | |
Heating capacity (A +2°C, W 35°C) | kW | 11,40 |
COP (A +2°C, W 35°C) | 3,44 | |
Heating capacity (A +2°C, W 55°C) | kW | 9,10 |
COP (A +2°C, W 55°C) | 2,20 | |
Heating capacity (A -7°C, W 35°C) | kW | 10,00 |
COP (A -7°C, W 35°C) | 2,73 | |
Heating capacity (A -7°C, W 55°C) | kW | 8,20 |
COP (A -7°C, W 55°C) | 1,92 | |
Cooling capacity (A 35°C, W 7°C) | kW | 10,00 |
EER (A 35°C, W 7°C) | 2,81 | |
Cooling capacity (A 35°C, W 18°C) | kW | 10,00 |
EER (A 35°C, W 18°C) | 4,17 | |
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) | ηs % | 190 / 134 |
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) | SCOP | 4,83 / 3,43 |
Heating average climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A+++ / A++ |
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) | ηs % | 245 / 159 |
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) | SCOP | 6,20 / 4,05 |
Heating warm climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A+++ / A+++ |
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) | ηs % | 168 / 121 |
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) | SCOP | 4,28 / 3,10 |
Heating cold climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A++ / A+ |
Indoor unit | WH-SDC12H9E8 | |
Indoor sound pressure (Heat) | dB(A) | 33 |
Indoor sound pressure (Cool) | dB(A) | 33 |
Indoor dimension (Height) | mm | 892 |
Indoor dimension (Width) | mm | 500 |
Indoor dimension (Depth) | mm | 340 |
Indoor net weight | kg | 45 |
Water pipe connector | Inch | R 1¼ |
A class pump (Number of speeds) | Variable Speed | |
A class pump (Input power Min) | W | 34 |
A class pump (Input power Max) | W | 110 |
Heating water flow (∆T=5 K. 35°C) | L/min | 34,40 |
Capacity of integrated electric heater | kW | 9,00 |
Indoor recommended fuse | A | 15 / 30 |
Recommended cable size, supply 1 | mm² | 5 x 1,5 |
Recommended cable size, supply 2 | mm² | 5 x 1,5 |
Outdoor unit | WH-UD12HE8 | |
Outdoor sound power part load (Heat) (3) | dB(A) | 65 |
Outdoor sound power full load (Heat) | dB(A) | 69 |
Outdoor sound power full load (Cool) | dB(A) | 68 |
Outdoor dimension (Height) | mm | 1340 |
Outdoor dimension (Width) | mm | 900 |
Outdoor dimension (Depth) | mm | 320 |
Outdoor net weight | kg | 107 |
Refrigerant (R410A) / CO2 Eq. | kg / T | 2,55 / 5,324 |
Pipe diameter (Liquid) | Inch (mm) | 3/8 (9,52) |
Pipe diameter (Gas) | Inch (mm) | 5/8 (15,88) |
Pipe length range | m | 3 ~ 30 |
Elevation difference (in/out) | m | 20 |
Pipe length for additional gas | m | 10 |
Additional gas amount | g/m | 50 |
Operation range (Outdoor ambient) | °C | -20 ~ +35 |
Water outlet (Heat) | °C | 20 ~ 55 |